Designed by Dowse Engineering for ducted supply, exhaust and extraction applications.
Designed with mixed flow aluminium alloy impellers that allow for maximum airflow at high pressure levels, the axial fans from Cyclo Fans is made in Australia and offers improved efficiency over vertical mounted fans. Thanks to its compact designed casing, this fan can handle a large volume of air and is able to provide high pressure characteristics over a variety of flows.
Available in galvanised or powder coated finishes, and with a number of colour options to choose from, the axial fan is made from stock components and is available on short delivery. Three phase motor options only. Specialised motors for extra protection are available on request.
To learn more about the fan, get in touch today +61 3 9383 6668.
Model No. | Fan Speed Rev/Min | K.W | Amps | Volts | Approx Noise Level @ 3mtr (dBA) | Motor Shaft mm | IP Rating |
A/SAA-61-114-3P | 1400 | 1.1 | 2.37 | 415 | 70 | 24 | 55 |
A/SAA-61-154-3P | 1400 | 1.5 | 3.15 | 415 | 72 | 24 | 55 |
A/SAA-61-224-3P | 1400 | 2.2 | 4.55 | 415 | 73 | 28 | 55 |
A/SAA-61-404-3P | 1400 | 4.0 | 7.75 | 415 | 74 | 28 | 55 |
A | 550 / 600mm |
B | 460 / 510mm |
C | 610mm |
D | 30mm |
E | 680mm |
Typical Industries & Applications :
Hospitality | Commercial Kitchens, Food Trucks, Mobile Food Containers
Manufacturing | Welding, Powder Coating, Spray Painting, Glue Works, Fibre Glassing
Warehousing / Office | Ablution Block, Heat Extraction
Extraction of Heat, Toxic Gas and Hazardous Gas options
Description | Axial (In-line) |
Model | A61 / SAA61 |
Int. Flange Dia | 610 mm |
Fixing | Roof Mounted, In-line |
Features | High performing, robust and light weight Locally owned and manufactured in Melbourne (Australia) since 1947 EPA Compliant, Australian & NZ Standards Compliant |
Impeller | Each impeller is individually designed and manufactured to precise specifications for maximum airflow at high pressure Hand crafted and balanced Aluminium alloy Mixed flow type impellers (axial flow and centrifugal design) |
Enclosure | Galvanized steel casing and waste resistant motor enclosures Motor mounted outside airstream Supplied with associated flanges |
Motor | Typical WEG |
Phase(s) | Three Phase Only |
Custom Motors | Hazard Area Motors – Ex ‘d’ Flame, Ex ‘e’ Increased Safety, Ex ‘n’ Non-Sparking, Dust Ignition Proof, Bush Fire Code Compliant |
Circuit Breaker | Separate Current rated circuit breaker (IEC/EN 60947 approved) must be installed between the motor and building power supply. Circuit breaker overload should be set to suit motor’s amp draw. |
Control Option(s) | Cyclo VSD (Available) (Plug ins available: Temperature sensor, CO2 sensor, Airflow / Pressure sensor, Smoke sensor) |
Weight | Approx. 60-70kg |
Installation | Fan Unit: Roof Plumber, Canopy Maintenance / Installer Electrical Connections: Licensed electrician |
Transport | Top load only Ensure impeller has not been exposed to wet weather. Water inside the motor housing can cause damage to the motor. |